Room Air Cleaner CADR Calculator

Compare an air cleaner’s particle CADR with the volume of the room it serves.

MODEL WORKSPACE

Your room air cleaning inputs

Ideal well-mixed particle-removal scenario.

An explicit design scenario, not a personal infection-risk target.

Example values are shown. Change them to calculate your result.

YOUR RESULT

Room air cleaning report

250 m³/hour · CADR for chosen equivalent ACH

Room volume 50 m³; ideal well-mixed model

Same required CADR147.144445 cfm
Entered cleaner equivalent ACH5 per hour
Ideal 99% decay time at entered CADR55.262042 min
Room volume50 m³
Full result table
Calculated from the current values, with rounded display.
Ideal elapsed minInitial particle fraction %
0100
1043.459821
2018.88756
308.2085
403.567399
501.550385
600.673795
700.29283
800.127263
900.055308
1000.024037
1100.010446
1200.00454

Ideal well-mixed particle-removal scenario. CADR is pollutant-specific and depends on operating speed. This does not measure outdoor ventilation, remove all gases or predict infection probability. Clearance times assume no continuing source and effective mixing.

HEALTHWAVY AI

Let’s work it out.

Ask about this tool, enter your values, or understand your result.

Ask in your own language.

GET STARTED

How to use Room Air Cleaner CADR Calculator

  1. Compare an air cleaner’s particle CADR with the volume of the room it serves.
  2. The chosen ACH is an explicit design comparison, not a prescribed personal protection target.
  3. The actual CADR divided by room volume gives an equivalent particle-removal air-change rate.

Worked example

A 5 ×4 ×2.5 m room is 50 m³. At a chosen five equivalent ACH, required CADR is 250 m³/hour.

Formula, accuracy & limitations

Room volume = length × width × height. Required equivalent clean-air flow = volume × chosen ACH. Actual equivalent ACH = CADR(m³/hour)/volume. Convert cfm with 1 cfm = 1.69901079552 m³/hour. Ideal 99% decay time = ln(100)/ACH hours.

Ideal well-mixed particle-removal scenario. CADR is pollutant-specific and depends on operating speed. This does not measure outdoor ventilation, remove all gases or predict infection probability. Clearance times assume no continuing source and effective mixing.

The primary result is rounded to two decimal places. Calculation tables show up to four and supporting metrics up to six. Very small nonzero values use scientific notation. Display rounding is not fed back into the arithmetic.

Official source and method context ↗

Size the actual connected space

Compare an air cleaner’s particle CADR with the volume of the room it serves. Measure length, width and ceiling height in metres; open connected areas may need to be treated as part of the space. A floor-area claim based on a standard ceiling should not be silently applied to a high-ceiling room.

Keep the selected air-change assumption visible

The chosen ACH is an explicit design comparison, not a prescribed personal protection target. Multiplying it by volume gives equivalent clean-air flow in cubic metres per hour. A cleaner’s fan airflow is not automatically its CADR because filtration effectiveness also matters.

Distinguish filtration from outdoor ventilation

The actual CADR divided by room volume gives an equivalent particle-removal air-change rate. It does not tell you the outdoor-air flow, remove carbon dioxide or establish gas removal. The report therefore keeps room filtration separate from the CO₂ decay ventilation tool.

Treat a decay time as an ideal model

The ideal 99% time assumes clean-air delivery remains constant, the room is effectively mixed and no new particles are emitted. Furnishings, placement and ongoing sources can change real performance. No calculated time is a guarantee that a room is infection-free.

QUICK ANSWERS

Frequently asked questions

Can I enter fan airflow instead of CADR?

Airflow and effective clean-air delivery are different. Use the relevant pollutant CADR at the operating setting.

Does this measure outdoor air?

Equivalent filtered-air changes are not an outdoor ventilation measurement.

Is the clearance time guaranteed?

It is an ideal no-source, well-mixed model and not a certification of room safety.

Why include ceiling height?

The calculation uses room volume, so two rooms with the same floor area can require different flows.